Digital input
505-508
Bus
Control com-
mand
0
0
0
0
1
0
1
0
0
1
1
1
Logic or
[3] is selected if the control command in ques-
tion is to be activated when a signal is given (active
signal = 1) either via a control word or via a digital input.
Digital input
505-508
Bus
Control com-
mand
0
0
0
0
1
1
1
0
1
1
1
1
NOTE
Parameters 502-504 deal with stop func-
tions - see examples regarding 502
(coasting) below. Active stop command
"0".
Parameter 502 =
Logic and
Digital input
Bus
Control command
0
0
1 Coasting
0
1
0 Motor running
1
0
0 Motor running
1
1
0 Motor running
Parameter 502 =
Logic or
Digital input
Bus
Control command
0
0
1 Coasting
0
1
1 Motor running
1
0
1 Motor running
1
1
0 Motor running
506
Reversing
(REVERSING SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Bus (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See description under parameter 502.
Description of choice:
See description under parameter 502.
509
Bus jog 1
(BUS JOG 1 FREQ.)
Value:
0.0 - parameter 202
10.0 Hz
Function:
This is where to set a fixed speed (jog) that is activated
via the serial communication port.
This function is the same as in parameter 213.
Description of choice:
The jog frequency f
JOG
can be selected in the range
between f
MIN
(parameter 201) and f
MAX
(parameter
202).
510
Bus jog 2
(BUS JOG 2 FREQ.)
Value:
0.0 - parameter 202
10.0 Hz
Function:
This is where to set a fixed speed (jog) that is activated
via the serial communication port.
This function is the same as in parameter 213.
Description of choice:
The jog frequency f
JOG
can be selected in the range
between f
MIN
(parameter 201) and f
MAX
(parameter
202).
512
Telegram profile
(TELEGRAM PROFILE)
Value:
Fieldbus profile (FIELDBUS PROFILE)
[0]
FC Drive (FC DRIVE)
[1]
Function:
There is a choice of two different control word profiles.
Description of choice:
Select the desired control word profile.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
142
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......