Outputs
terminal no.
42
45
01(re-
lay)
04 (re-
lay)
parameter
319
321
323
326
Value:
No function
(NO OPERATION)
[0]
[0]
[0]
[0]
Control ready
(CONTROL READY)
[1]
[1]
[1]
[1]
Ready signal
(UNIT READY)
[2]
[2]
[2]
[2]
Ready - remote control
(UNIT READY/REM CTRL)
[3]
[3]
[3]
[3]
Enable, no warning
(ENABLE/NO WARNING)
[4]
[4]
[4]
[4]
Running
(VLT RUNNING)
[5]
[5]
[5]
[5]
Running, no warning
(RUNNING/NO WARNING)
[6]
[6]
[6]
[6]
Running within range, no warning
(RUN IN RANGE/NO WARN)
[7]
[7]
[7]
[7]
Running at reference value, no warning (RUN ON REF/NO WARN)
[8]
[8]
[8]
[8]
Fault
(ALARM)
[9]
[9]
[9]
[9]
Fault or warning
(ALARM OR WARNING)
[10]
[10]
[10]
[10]
Torque limit
(TORQUE LIMIT)
[11]
[11]
[11]
[11]
Out of current range
(OUT OF CURRENT RANGE)
[12]
[12]
[12]
[12]
Over I low
(ABOVE CURRENT,LOW)
[13]
[13]
[13]
[13]
Under I high
(BELOW CURRENT,HIGH)
[14]
[14]
[14]
[14]
Out of frequency range
(OUT OF FREQ RANGE)
[15]
[15]
[15]
[15]
Over f low
(ABOVE FREQUENCY LOW)
[16]
[16]
[16]
[16]
Under f high
(BELOW FREQUENCY HIGH)
[17]
[17]
[17]
[17]
Out of feedback range
(OUT OF FDBK RANGE)
[18]
[18]
[18]
[18]
Over feedback low
(ABOVE FDBK, LOW)
[19]
[19]
[19]
[19]
Under feedback high
(BELOW FDBK, HIGH)
[20]
[20]
[20]
[20]
Thermal warning
(THERMAL WARNING)
[21]
[21]
[21]
[21]
Ready - no thermal warning
(READY & NOTHERM WARN)
[22]
[22]
[22]
[22]
Ready - remote control - no therm. warn. (REM RDY & NO THERMWAR)
[23]
[23]
[23]
[23]
Ready - mains voltage within range
(RDY NO OVER/UNDERVOL)
[24]
[24]
[24]
[24]
Reversing
(REVERSE)
[25]
[25]
[25]
[25]
Bus ok
(BUS OK)
[26]
[26]
[26]
[26]
Torque limit and stop
(TORQUE LIMIT AND STOP)
[27]
[27]
[27]
[27]
Brake, no brake warning
(BRAKE NO BRAKE WARNING)
[28]
[28]
[28]
[28]
Brake ready, no fault
(BRAKE RDY (NO FAULT))
[29]
[29]
[29]
[29]
Brake fault
(BRAKE FAULT (IGBT))
[30]
[30]
[30]
[30]
Relay 123
(RELAY 123)
[31]
[31]
[31]
[31]
Mechanical brake control
(MECH. BRAKE CONTROL)
[32]
[32]
[32]
[32]
Control word bit 11/12
(CTRL WORD BIT 11/12)
[33]
[33]
Extended mechanical brake control
(EXT. MECH. BRAKE)
[34]
[34]
[34]
[34]
Safety interlock
(SAFETY INTERLOCK)
[35]
[35]
[35]
[35]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
117
Progra
mming
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......