Parameter
no.
Description
Display
text
Unit
Updating
interval
515
Reference %
(REFERENCE)
%
80 msec.
516
Reference Unit
(REFERENCE [UNIT])
Hz, Nm or rpm
80 msec.
517
Feedback
(FEEDBACK)
To be selected via
par. 416
80 msec.
518
Frequency
(FREQUENCY)
Hz
80 msec.
519
Frequency x Scaling
(FREQUENCY X SCALE)
-
80 msec.
520
Current
(MOTOR CURRENT)
Amp x 100
80 msec.
521
Torque
(TORQUE)
%
80 msec.
522
Power, kW
(POWER (KW)
kW
80 msec.
523
Power, HP
(POWER (HP)
HP (US)
80 msec.
524
Motor voltage
(MOTOR VOLTAGE)
V
80 msec.
525
DC link voltage
(DC LNK VOLTAGE)
V
80 msec.
526
Motor temp.
(MOTOR THERMAL)
%
80 msec.
527
VLT temp.
(VLT THERMAL)
%
80 msec.
528
Digital input
(DIGITAL INPUT)
Binary code
2 msec.
529
Terminal 53, analogue in-
put
(ANALOG INPUT 53)
V
20 msec.
530
Terminal 54, analogue in-
put
(ANALOG INPUT 54)
V
20 msec.
531
Terminal 60, analogue in-
put
(ANALOG INPUT 60)
mA
20 msec.
532
Pulse reference
(PULSE REFERENCE)
Hz
20 msec.
533
External reference %
(EXT. REFERENCE)
20 msec.
534
Status word
(STATUS WORD [HEX])
Hex code
20 msec.
535
Brake power/2 min.
(BR. ENERGY/2 MIN)
kW
536
Brake power/sec.
(BRAKE ENERGY/S)
kW
537
Heat sink temperature
(HEATSINK TEMP.)
°C
1.2 sec.
538
Alarm word
(ALARM WORD [HEX])
Hex code
20 msec.
539
VLT control word
(CONTROLWORD [HEX])
Hex code
2 msec.
540
Warning word, 1
(WARN. WORD 1)
Hex code
20 msec.
541
Extended status word Hex (EXT. STATUS WORD)
Hex code
20 msec.
557
Motor RPM
(MOTOR RPM)
RPM
80 msec.
558
Motor RPM x scaling
(MOTOR RPM X SCALE)
-
80 msec.
Function:
These parameters can be read out via the serial com-
munication port and via the display in Display mode,
see also parameters 009 - 012.
Description of choice:
Reference %, parameter 515:
The value shown corresponds to rhe total reference
(sum of digital/analogue/preset/bus/freeze ref./catch-
up and slow-down).
Reference Unit, parameter 516:
Gives the present value of terminals 17/29/53/54/60 in
the unit resulting from the choice of configuration in
parameter 100 (Hz, Nm or rpm) or in parameter 416.
See also parameters 205 and 416, if required.
Feedback, parameter 517:
Indicates the status value of terminals 33/53/60 at the
unit/scale selected in parameters 414, 416 and 416.
Frequency, parameter 518:
The value shown corresponds to the actual motor fre-
quency f
M
(without resonance dampening).
Frequency x scale, parameter 519:
The value shown corresponds to the actual motor fre-
quency f
M
(without resonance dampening) multiplied
by a factor (scaling) set in parameter 008.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
144
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......