Mechanical installation
Mechanical installation
Please pay attention to the requirements
that apply to integration and field mount-
ing kit, see the below list. The information
given in the list must be observed to avoid
serious damage or injury, especially when
installing large units.
The frequency converter
must
be installed vertically.
The frequency converter is cooled by means of air cir-
culation. For the unit to be able to release its cooling
air, the
minimum
distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be ensur-
ed that the ambient temperature
does not rise above
the max. temperature stated for the frequency convert-
er
and that the 24-hour average temperature
is not
exceeded
. The max. temperature and 24-hour average
can be seen from the
General Technical Data
.
If the ambient temperature is in the range of 45°C -55°
C, derating of the frequency converter will become rel-
evant, see
Derating for ambient temperature
.
The service life of the frequency converter will be re-
duced if derating for ambient temperature is not taken
into account.
Installation of VLT 5001-5602
All frequency converters must be installed in a way that
ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side by side/
flange by flange.
VLT
®
5000 Series
44
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......