PNU
Parameter
Factory setting
Range
Changes 4-Setup
Conver-
sion
Data
#
description
during operation
index
type
200
Output frequency range/direction Only clockwise, 0-132 Hz
No
Yes
0
5
201
Output frequency low limit
0.0 Hz
0.0 - f
MAX
Yes
Yes
-1
6
202
Output frequency high limit
66 / 132 Hz
f
MIN
- par. 200
Yes
Yes
-1
6
203
Reference/feedback area
Min - max
Yes
Yes
0
5
204
Minimum reference
0.000
-100,000.000-Ref
MAX
Yes
Yes
-3
4
205
Maximum reference
50.000
Ref
MIN
-100,000.000
Yes
Yes
-3
4
206
Ramp type
Linear
Yes
Yes
0
5
207
Ramp-up time 1
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
208
Ramp-down time 1
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
209
Ramp-up time 2
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
210
Ramp-down time 2
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
211
Jog ramp time
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
212
Quick stop ramp-down time
Depends on unit
0.05 - 3600
Yes
Yes
-2
7
213
Jog frequency
10.0 Hz
0.0 - par. 202
Yes
Yes
-1
6
214
Reference function
Sum
Yes
Yes
0
5
215
Preset reference 1
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
216
Preset reference 2
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
217
Preset reference 3
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
218
Preset reference 4
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
219
Catch up/slow down value
0.00 %
0.00 - 100 %
Yes
Yes
-2
6
220
221
Torque limit for motor mode
160 %
0.0 % - xxx %
Yes
Yes
-1
6
222
Torque limit for regenerative op-
eration
160 %
0.0 % - xxx %
Yes
Yes
-1
6
223
Warning: Low current
0.0 A
0.0 - par. 224
Yes
Yes
-1
6
224
Warning: High current
I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes
Yes
-1
6
225
Warning: Low frequency
0.0 Hz
0.0 - par. 226
Yes
Yes
-1
6
226
Warning: High frequency
132.0 Hz
Par. 225 - par. 202
Yes
Yes
-1
6
227
Warning: Low feedback
-4000.000
-100,000.000 - par. 228 Yes
-3
4
228
Warning: High feedback
4000.000
Par. 227 - 100,000.000
Yes
-3
4
229
Frequency bypass, bandwidth
OFF
0 - 100 %
Yes
Yes
0
6
230
Frequency bypass 1
0.0 Hz
0.0 - par. 200
Yes
Yes
-1
6
231
Frequency bypass 2
0.0 Hz
0.0 - par. 200
Yes
Yes
-1
6
232
Frequency bypass 3
0.0 Hz
0.0 - par. 200
Yes
Yes
-1
6
233
Frequency bypass 4
0.0 Hz
0.0 - par. 200
Yes
Yes
-1
6
234
Motor phase monitor
Enable
Yes
Yes
0
5
VLT
®
5000 Series
222
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......