414
Minimum feedback
(MIN. FEEDBACK)
Value:
-100,000.000 - Max. feedback
0.000
Function:
Parameters 414 and 415 are used to scale the display
text to make it show the feedback signal as the actual
unit proportional to the signal on the input. This value
will be displayed if
Feedback [unit]
[3] has been selec-
ted in one of parameters 009-012 and in the display
mode. Choose the feedback signal unit in parameter
416.
Used together with
Speed control, closed-loop; Proc-
ess control, closed-loop
and
Torque control speed
feedback
, (parameter 100).
Description of choice:
Is only active when parameter 203 has been set to
Min-Max
[0].
Set the value to be shown on the display when
Mini-
mum feedback is obtained on the selected feedback
input (parameter 308 or 314).
The minimum value can be limited by the choice of
configuration (parameter 100) and reference/feedback
range (parameter 203).
If
Speed control, closed-loop
[1] has been selected in
parameter 100, minimum feedback cannot be set un-
der 0.
415
Maximum feedback
(MAX. FEEDBACK)
Value:
Min. feedback - 100,000.000
1,500.000
Function:
This value should be 10% higher than par. 205
Maxi-
mum reference
, to keep the adjustable frequency drive
from integrating as a response to a possible offset
fault.
For further description, see parameter 414.
Description of choice:
Set the value to be shown on the display when
Maxi-
mum feedback is obtained on the selected feedback
input (parameter 308 or 314)
. The maximum value can
be limited by the choice of configuration (parameter
100).
416
Reference/feedback unit
(REF/FEEDB. UNIT)
Value:
NO UNIT
[0]
%
[1]
PPM
[2]
RPM
[3]
bar
[4]
CYCLE/min
[5]
PULSE/s
[6]
UNITSS/s
[7]
UNITS/min
[8]
UNITS/h
[9]
°C
[10]
Pa
[11]
l/s
[12]
m
3
/s
[13]
l/min
[14]
m
3
/min
[15]
l/h
[16]
m
3
/h
[17]
kg/s
[18]
kg/min
[19]
kg/h
[20]
t/min
[21]
t/h
[22]
m
[23]
N m
[24]
m/s
[25]
m/min
[26]
°F
[27]
in wg
[28]
gal/s
[29]
ft
3
/s
[30]
gal/min
[31]
ft
3
/min
[32]
gal/h
[33]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
130
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...