Function:
This parameter determines the value of the reference
signal that is to correspond to the minimum reference
value set in parameter 204.
If the timeout function of parameter 317 is used, the
value must be set at >2 mA.
Description of choice:
Set the desired current value.
See also section
Handling of
single references.
316
Terminal 60, max. scaling
(AI 60 SCALE HIGH)
Value:
0.0 - 20.0 mA
20.0 mA
Function:
This parameter sets the value of the reference signal
that is to correspond to the maximum reference value
set in parameter 205.
Description of choice:
Set the desired current value.
See also section
Handling of single references
.
317
Time out
(LIVE ZERO TIME O)
Value:
0 - 99 sec.
10 sec.
Function:
If the signal value of the reference signal connected to
the input, terminal 60, falls below 50% of the value set
in parameter 315 for a period longer than the time set
in parameter 317, the function selected in parameter
318 will be activated.
Description of choice:
Set the desired time.
318
Function after time out
(LIVE ZERO FUNCT.)
Value:
Off (OFF)
[0]
Freeze output frequency (FREEZE OUTPUT
FREQ.)
[1]
Stop (STOP)
[2]
Jog (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter allows a choice of the function to be
activated if the input signal on terminal 60 drops below
2 mA, provided parameter 315 has been set higher
than 2 mA and that the preset time for time-out (pa-
rameter 317) has been exceeded.
If more time-outs occur at the same time the adjustable
frequency drive will give the following priority to the
time-out function:
1.
Parameter 318
Function after time out
2.
Parameter 346
Function after encoder loss
3.
Parameter 514
Bus time interval function
Description of choice:
The output frequency of the adjustable frequency drive
can be:
-
frozen at the present value
-
overruled to stop
-
overruled to jog frequency
-
overruled to max. frequency
-
overruled to stop with subsequent trip.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
116
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......