Application configuration
Using this parameter enables the choice of a configu-
ration (setting) of the adjustable frequency drive that
fits the application in which the adjustable frequency
drive is to be active.
NOTE
First, the motor nameplate date must be
set in parameters 102-106.
There is a choice of the following configurations:
-
Speed control, open loop
-
Speed control, closed loop
-
Process control, closed loop
-
Torque control, open loop
-
Torque control, speed feedback
The selection of special motor characteristics can be
combined with any application configuration.
Setting of parameters
Select
Speed control, open loop
if a normal speed ad-
justment without external feedback signals is required
(the internal slip compensation is operating) from mo-
tor or unit.
Set the following parameters in order shown:
Speed control, open loop:
Parameter:
Setting:
Data value:
100
Configuration
Speed control, open loop
[0]
200
Output frequency range/direction
201
Output frequency low limit
Only if [0] or [2] in par. 200
202
Output frequency high limit
203
Reference/feedback range
204
Minimum reference
Only if [0] in par. 203
205
Maximum reference
Select
Speed control, closed loop
if the application has
a feedback signal and the accuracy in
Speed control,
open loop
is not sufficient or a full holding torque is
required.
Set the following parameters in order shown:
Speed control, closed loop (PID):
Parameter:
Setting:
Data value:
100
Configuration
Speed control, closed loop
[1]
200
Output frequency range/direction
Output frequency low limit
201
Output frequency low limit
202
Output frequency high limit
203
Reference/feedback range
414
Minimum feedback
Only if [0] or [2] in par. 200
415
Maximum feedback
204
Minimum reference
Only if [0] in par. 203
205
Maximum reference
417
Speed PID proportional gain
418
Speed PID integration time
419
Speed PID differentiation time
420
Speed PID diff. gain limit
421
Speed PID lowpass filter time
Please be aware that the encoder loss function (pa-
rameter 346) will be active when parameter 100 is set
to
Speed control, closed loop.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
185
List of functions
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......