454
Dead time compensation
(DEADTIME COMP.)
Value:
Off (OFF)
[0]
On (ON)
[1]
Function:
The active inverter dead time compensation which is
part of the VLT 5000 control algorithm (VVC+) is caus-
ing instability at standstill when working in closed-loop
control. The purpose of this parameter is switching off
the active dead time compensation to avoid instability.
Description of choice:
Select
Off
[0] to inactivate the dead time compensa-
tion.
Select
On
[1] to activate the dead time compensation.
455
Frequency range monitor
(MON. FREQ. RANGE)
Value:
Disable
[0]
Enable
[1]
Function:
This parameter is used if warning 35
Out of frequency
range
must be turned off in the display in process con-
trol closed loop. This parameter does not affect the
extended status word.
Description of choice:
Select
Enable
[1] to enable the readout in the display
if warning 35
Out of frequency range
occurs. Select
Disable
[0] to disable the readout in the display if warn-
ing 35
Out of frequency range
occurs.
457
Phase loss function
(Phase loss funct)
Value:
Trip (Trip)
[0]
Warning (Warning)
[1]
Function:
Select the function which is to be activated if the mains
imbalance becomes too high or if a phase is missing.
Description of choice:
At
Trip
[0] the adjustable frequency drive will stop the
motor within a few seconds (depending on drive size).
At
Warning
[1] only a warning will be exported when a
mains failure occurs, but in severe cases, other ex-
treme conditions might result in a trip.
NOTE
If
Warning
has been selected, the life ex-
pectancy of the drive will be reduced when
the mains failure persists.
NOTE
At phase loss, the internal cooling fans of
some drive types cannot be powered. In
order to avoid overheating, an external
power supply can be connected.
IP00/IP20/NEMA
- VLT 5032-5052, 200-240 V
- VLT 5122-5552, 380-500 V
- VLT 5042-5602, 525-690 V
- IP54
- VLT 5006-5052, 200-240 V
- VLT 5016-5552, 380-500 V
- VLT 5042-5602, 525-690 V
See also
Electrical Installation.
483
Dynamic DC link compensation
(DC link comp.)
Value:
Off
[0]
On
[1]
Function:
The adjustable frequency drive includes a feature,
which ensures that the output voltage is independent
of any voltage fluctuation in the DC link, e.g. caused
by fast fluctuation in the mains supply voltage. The
benefit is a very steady torque on motor shaft (low tor-
que ripple) under most mains conditions.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
139
Progra
mming
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......