Compact, AC line supply 3 x 200-240 V
According to international requirements
VLT type
5008
5011
5016
5022
5027
Normal overload torque (110 %):
Output current
I
VLT,N
[A]
32
46
61.2
73
88
I
VLT, MAX
(60 s)
[A]
35.2
50.6
67.3
80.3
96.8
Output (240 V)
S
VLT,N
[kVA]
13.3
19.1
25.4
30.3
36.6
Typical shaft output
P
VLT,N
[kW]
7.5
11
15
18.5
22
Typical shaft output
P
VLT,N
[HP]
10
15
20
25
30
High overload torque (160 %):
Output current
I
VLT,N
[A]
25
32
46
61.2
73
I
VLT, MAX
(60 s)
[A]
40
51.2
73.6
97.9
116.8
Output (240 V)
S
VLT,N
[kVA]
10
13
19
25
30
Typical shaft output
P
VLT,N
[kW]
5.5
7.5
11
15
18.5
Typical shaft output
P
VLT,N
[HP]
7.5
10
15
20
25
Max. cable cross-section to motor,
IP 54
16/6 16/6
35/2
35/2
50/0
brake and load sharing [mm
2
/AWG]
2) 5)
IP 20
16/6 35/2
35/2
35/2
50/0
Min. cable cross-section to motor, brake and
load sharing
4)
[mm
2
/AWG]
2)
10/8 10/8
10/8
10/8
16/6
Rated input current
(200 V) I
L,N
[A]
32
46
61
73
88
Max. cable cross-section,
IP 54
16/6 16/6
35/2
35/2
50/0
power [mm
2
]/[AWG]
2) 5)
IP 20
16/6 35/2
35/2
35/2
50/0
Max. pre-fuses
[-]/UL
1)
[A]
50
60
80
125
125
Efficiency
3)
0.95
0.95
0.95
0.95
0.95
Weight IP 20 EB
[kg]
21
25
27
34
36
Weight IP 54
[kg]
38
40
53
55
56
Power loss at max. load.
- high overload torque
(160 %)
[W]
340
426
626
833
994
- normal overload torque
(110 %)
[W]
426
545
783
1042
1243
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
5. Aluminum cables with cross-section above 0.054 in
2
[35 mm
2
] must be connected by use of an AI-Cu connector.
VLT
®
5000 Series
14
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......