however, the adjustable frequency drive can also be
controlled via the digital inputs.
For selections [1-2] control is shifted to open loop, no
slip compensation.
Local control as parameter 100
[3] is used when the
motor speed is to be set via parameter 003
Local ref-
erence
, but without parameter 100
Configuration
auto-
matically shifting to
Speed regulation, open loop
[0].
Remote-operated control as parameter 100
[4] works
the same way as
Local control as parameter 100
[3];
however, the adjustable frequency drive can also be
controlled via the digital inputs.
Shifting from
Remote operation
to
Local operation
in
parameter 002
Local/remote operation
, while this pa-
rameter has been set to
Remote-operated control and
open loop
[1]: The present motor frequency and direc-
tion of rotation will be maintained. If the present direc-
tion of rotation does not respond to the reversing signal
(negative reference), the reference will be set to 0.
Shifting from
Local operation
to
Remote operation
in
parameter 002
Local/remote control
, while this param-
eter has been set to
Remote-operated control and open
loop
[1]: The configuration selected in parameter 100
Configuration
will be active. The shift will be smooth.
Shifting from
Remote control
to
Local control
in param-
eter 002
Local/remote operation
, while this parameter
has been set to
Remote-operated control as parameter
100
[4]: the present reference will be maintained. If the
reference signal is negative, the local reference will be
set to 0.
Shifting from
Local operation
to
Remote operation
in
parameter 002
Local/remote operation
, while this pa-
rameter has been set to
Remote operation
: The local
reference will be replaced by the remote-operated ref-
erence signal.
014
Local stop
(LOCAL STOP)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the local [STOP]-key can be engag-
ed or disengaged on the control panel and on the LCP
control panel.
Description of choice:
If
Not active
[0] is selected in this parameter, the
[STOP]-key will be inactive.
NOTE
If
Not active
[0] is selected, the motor can-
not be stopped by means of the [STOP]-
key.
015
Local jog
(LOCAL JOGGING)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the jog function on the LCP control
panel can be engaged/disengaged.
Description of choice:
If
Not active
[0] is selected in this parameter, the [JOG]-
key will be inactive.
016
Local reverse
(LOCAL REVERSE)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select/deselect the reverse
function on the LCP control panel. The key can only
be used if parameter 002
Local/remote operation
is set
to
Local operation
[1] and parameter 013
Localcon-
trol
to
Local control, open loop
[1] or
Local control as
parameter 100
[3].
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port