Special functions
400
Brake function
(Brake function)
Value:
Off (off)
[0]
Resistor brake
(Resistor)
[1]
AC brake (AC Brake)
[4]
Load sharing (load sharing)
[5]
Factory setting depends on unit type.
Function:
Resistor brake
[1] is selected if the adjustable frequen-
cy drive has an integral brake transistor and brake
resistor is connected to terminals 81, 82. A higher in-
termediate circuit voltage is permitted during braking
(generated operation) when a brake resistor is con-
nected.
AC brake
[4] can be selected to improve braking with-
out using brake resistors. Please note that
AC brake
[4] is not as effective as
Resistor brake
[1].
Description of choice:
Select
Resistor brake
[1] if a brake resistor is connec-
ted.
Select
AC brake
[4] if short-term generated loads oc-
cur. See parameter 144
Gain AC brake
to set the brake.
Select
Load sharing
[5] if this is used.
NOTE
A change of selection will not become ac-
tive until the mains voltage has been dis-
connected and reconnected.
405
Reset function
(reset mode)
Value:
Manual reset (manual reset)
[0]
Automatic reset x 1
(AUTOMATIC x 1)
[1]
Automatic reset x 3
(AUTOMATIC x 3)
[3]
Automatic reset x 10
[10]
(AUTOMATIC x 10)
Reset at power-up
(RESET AT POWER UP)
[11]
Function:
This parameter makes it possible to select whether re-
set and restart after a trip are to be manual or whether
the adjustable frequency drive is to be reset and re-
started automatically. Furthermore, it is possible to
select the number of times a restart is to be attempted.
The time between each attempt is set in parameter 406
Automatic restart time
.
Description of choice:
If
Manual reset
[0] is selected, reset is to be carried out
via the [STOP/RESET] key, a digital input or serial
communication. If the adjustable frequency drive is to
carry out an automatic reset and restart after a trip,
select data value [1], [3] or [10].
If
Reset at power-up
[11] is selected, the adjustable
frequency drive will carry out a reset if there has been
a fault in connection with the mains failure.
The motor may start without warning.
406
Automatic restart time
(autorestart time)
Value:
0 - 10 sec.
5 sec.
Function:
This parameter allows setting of the time from tripping
until the automatic reset function begins. It is assumed
that automatic reset has been selected in parameter
405
Reset function
.
Description of choice:
Set the required time.
409
Trip delay overcurrent, I
LIM
(trip delay cur.)
Value:
0 - 60 sec. (61=OFF)
OFF
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark
69