References & Limits
200
Output frequency range
(OUT FREQ. RNG/ROT)
Value:
Only clockwise, 0 - 132 Hz
(132 Hz CLOCKWISE)
[0]
Both directions, 0 - 132 Hz
(132 Hz BOTH DIRECT)
[1]
Counter-clockwise only, 0 - 132 Hz
(132 Hz COUNTER CLOCK)
[2]
Clockwise only, 0 - 1,000 Hz
(1,000 Hz CLOCK WISE)
[3]
Both directions, 0 - 1,000 Hz
(1,000 Hz BOTH DIRECT)
[4]
Counter-clockwise only, 0 - 1,000 Hz
(1,000 Hz COUNTER CLOCK)
[5]
Function:
This parameter guarantees protection against unwan-
ted reversing. Furthermore, the maximum output fre-
quency that is to apply regardless of the settings of
other parameters can be selected. This parameter has
no function if
Process regulation, closed-loop
has been
selected in parameter 100
Configuration
.
Description of choice:
Select the required direction of rotation as well as the
maximum output frequency. Please note that if
Clock-
wise only
[0]/[3] or
Counter-clockwise only
[2]/[5] is
selected, the output frequency will be limited to the
range f
MIN
-f
MAX
. If
Both directions
[1]/[4] is selected, the
output frequency will be limited to the range ± f
MAX
(the
minimum frequency is of no significance).
201
Output frequency low limit, f
MIN
(MIN OUTPUT FREQ)
Value:
0.0 - f
MAX
0.0 Hz
Function:
In this parameter, a minimum motor frequency limit
can be selected that corresponds to the minimum
speed at which the motor is allowed to run. If
Both di-
rections
has been selected in parameter 200
Output
frequency range
, the minimum frequency is of no sig-
nificance.
Description of choice:
The value chosen can range from 0.0 Hz to the fre-
quency set in parameter 202
Output frequency high
limit, f
MAX
.
202
Output frequency high limit, f
MAX
(max. output freq)
Value:
f
MIN
- 132/1,000 Hz (par. 200
Output fre-
quency range
)
132 Hz
Function:
In this parameter, a maximum output frequency limit
can be selected that corresponds to the highest speed
at which the motor is allowed to run.
NOTE
The output frequency of the adjustable
frequency drive can never assume a value
higher than 1/10 of the switching frequen-
cy (parameter 411
Switching frequency
).
Description of choice:
A value can be selected from f
MIN
to the value chosen
in parameter 200
Output frequency range
.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port