Alarm 44, internal fault number 7: Minimum software
version of control card or BMC.
Alarm 45, internal fault number 8: I/O fault (digital in-
put/output, relay or analog input/output).
NOTE
When restarting after an alarm 38-45, the
adjustable frequency drive will display an
alarm 37. In parameter 615 the actual
alarm code can be read.
ALARM 50: AMT not possible
One of the following three possibilities can occur:
-
The calculated R
S
value falls outside permit-
ted limits.
-
The motor current in at least one of the motor
phases is too low.
-
The motor in use is too small for AMT calcu-
lations to be performed.
ALARM 51: AMT Fault regarding nameplate data
There is inconsistency between the registered motor
data. Check the motor data for the relevant setup.
ALARM 52: AMT missing motor phase
The AMT function has detected a missing motor
phase.
ALARM 55: AMT timeout
Calculations are taking too long, possibly due to noise
on the motor cables.
ALARM 56: AMT warning during AMT
A adjustable frequency drive warning is given while
AMT is being performed.
WARNING 99: Locked
See parameter 18.
Alarm/warning limits:
Without brake
With brake
Without brake
With brake
VLT 2800
1 / 3 x 200 - 240 V
[VDC]
1 / 3 x 200 - 240 V
[VDC]
3 x 380 - 480 V
[VDC]
3 x 380 - 480 V
[VDC]
Undervoltage
215
215
410
410
Voltage warning low
230
230
440
440
Voltage warning high
385
400
765
800
Overvoltage
410
410
820
820
The voltages stated are the intermediate circuit volt-
age of the adjustable frequency drive with a tolerance
of ± 5 %. The corresponding line voltage is the inter-
mediate circuit voltage divided by 1,35.