3.2.5 Control Structure in Flux Sensorless (AutomationDrive FC 302 only)
Control structure in flux sensorless open-loop and closed-loop configurations.
In the shown configuration, par. 1-01
Motor Control Principle
is set to “Flux sensorless [2]” and par. 1-00
Configuration Mode
is set to “Speed open-loop
[0]”. The resulting reference from the reference handling system is fed through the ramp and speed limitations as determined by the parameter settings
indicated.
An estimated speed feedback is generated to the speed PID to control the output frequency.
The Speed PID must be set with its P,I, and D parameters (par. group 7-0*).
Select “Process [3]” in par. 1-00
Configuration Mode
to use the process PID control for closed-loop control of, e.g., speed or pressure in the controlled
application. The Process PID parameters are found in par. group 7-2* and 7-3*.
FC 300 Design Guide
3 Introduction to AutomationDrive FC 300
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
3-7