8.11.1 Residual Current Device
You can use RCD relays, multiple protective grounding or grounding as extra protection, provided that local safety regulations are complied with.
If a ground fault appears, a DC content may develop in the faulty current.
If RCD relays are used, you must observe local regulations. Relays must be suitable for protection of 3-phase equipment with a bridge rectifier and for
a brief discharge on power-up see section
Ground Leakage Current
for further information.
8 Electrical Installation
FC 300 Design Guide
8-50