![Danfoss FC 300 Скачать руководство пользователя страница 112](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599112.webp)
AutomationDrive FC 302 - Line power: 525–600 V (T6) - 10% Duty Cycle
Automation
Drive FC 302
P
m (HO)
R
min
R
br, nom
R
rec
P
br avg
Order no.
Period
Cable cross-
section
2
*
Therm.
relay
Max. brake torque
with R
rec
*
T6
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm2]
[A]
[%]
PK75
0.75
620
904
620
0.1
1840
120
1.5
0.3
160 (160)
P1K1
1.1
550
613
620
0.1
1840
120
1.5
0.3
160 (160)
P1K5
1.5
380
447
425
0.1
1841
120
1.5
0.5
160 (160)
P2K2
2.2
270
301
310
0.3
1842
120
1.5
0.9
160 (160)
P3K0
3
189
218
210
0.3
1843
120
1.5
1.2
160 (160)
P4K0
4
135
162
150
0.4
1844
120
1.5
1.7
160 (160)
P5K5
5.5
99
116
110
0.6
1845
120
1.5
2.3
160 (160)
P7K5
7.5
72
84.5
80
0.9
1846
120
1.5
3.3
160 (160)
P11K
11
40
57
40
2
1848
120
1.5
3.9
160 (160)
P15K
15
36
41.3
40
2
1848
120
1.5
7.1
160 (160)
P18K
18.5
27
33.2
30
2.8
1849
120
1.5
9.7
160 (160)
P22K
22
22.5
27.6
25
3.5
1850
120
1.5
12
150 (150)
P30K
30
18
21.6
20
4
1851
120
1.5
14
150 (150)
P37K
37
13.5
17.3
15
4.8
1852
120
2.5
18
150 (150)
P45K
45
10.8
14.2
12
5.5
1853
120
2.5
21
150 (150)
P55K
55
8.8
11.6
9.8
15
2008
120
10
39
150 (150)
P75K
75
6.6
8.4
7.3
13
0069
120
10
42
150 (150)
P90K
90
4.7
7
4.7
18
1959
300
16
62
150 (150)
P110
110
4.7
5.8
4.7
18
1959
300
16
62
150 (150)
P132
132
4.2
4.8
4.7
18
1959
300
16
62
150 (150)
P160
160
3.4
4
3.8
22
1960
300
25
76
150 (150)
P200
200
2.7
3.2
5.2 / 2 = 2.6
36 x 2 = 72
2 x 1062
300
2 x 70
5
*
166
150 (150)
P250
250
2.2
2.5
5.2 / 2 = 2.6
36 x 2 = 72
2 x 1062
300
2 x 70
5
*
166
146 (150)
P315
315
1.7
2
(150)
P355
355
1.6
1.8
(150)
P400
400
1.4
1.6
(150)
P450
450
1.2
1.3
(150)
P500
500
1.2
1.3
(150)
P560
560
1.2
1.3
(130)
P670
670
1.2
1.3
(116)
P750
750
1.2
1.3
(103)
P850
850
1.2
1.3
(91)
P1M0
1000
1.2
1.3
(73)
P1M1
1100
1.2
1.3
5 How to Order
FC 300 Design Guide
5-12
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
5