8.4.3 F Frame Circuit Breakers
Frame size
Power & Voltage
Type
F3
P450 380–500 V & P630-P710 525–690 V
Merlin Gerin NPJF36120U31AABSCYP
F3
P500-P630 380–500 V & P800 525–690 V
Merlin Gerin NRJF36200U31AABSCYP
F4
P710 380–500 V & P900-P1M0 525–690 V
Merlin Gerin NRJF36200U31AABSCYP
F4
P800 380–500 V
Merlin Gerin NRJF36250U31AABSCYP
8.4.4 F-Frame Line Power Contactors
Frame size
Power & Voltage
Type
F3
P450-P500 380–500 V & P630-P800 525–690 V
Eaton XTCE650N22A
F3
P560 380–500 V
Eaton XTCE820N22A
F3
P630380–500 V
Eaton XTCEC14P22B
F4
P900 525–690 V
Eaton XTCE820N22A
F4
P710-P800 380–500 V & P1M0 525–690 V
Eaton XTCEC14P22B
8.5 Additional Motor Information
8.5.1 Motor Cable
The motor must be connected to terminals U/T1/96, V/T2/97, W/T3/98. Ground to terminal 99. All types of three-phase asynchronous standard motors
can be used with an adjustable frequency drive unit. The factory setting is for clockwise rotation with the adjustable frequency drive output connected
as follows:
Terminal No.
Function
96, 97, 98, 99
Line power U/T1, V/T2, W/T3
Ground
• Terminal U/T1/96 connected to U-phase
• Terminal V/T2/97 connected to V-phase
• Terminal W/T3/98 connected to W-phase
The direction of rotation can be changed by switching two phases in the motor cable or by changing the setting of par. 4-10
Motor Speed Direction
.
Motor rotation check can be performed using par. 1-28
Motor Rotation Check
and following the steps shown in the display.
FC 300 Design Guide
8 Electrical Installation
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
8-29