Line Power Supply 3 x 525–690 V AC
AutomationDrive FC
302
P30K
P37K
P45K
P55K
P75K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at
550 V [kW]
22
30
30
37
37
45
45
55
55
75
Typical Shaft output at
575 V [HP]
30
40
40
50
50
60
60
75
75
100
Typical Shaft output at
690 V [kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP21, 55
C2
C2
C2
C2
C2
Output current
Continuous
(3 x 525–550 V) [A]
36
43
43
54
54
65
65
87
87
105
Intermittent (60 sec
overload)
(3 x 525–550 V) [A]
54
47.3
64.5
59.4
81
71.5
97.5
95.7
130.5
115.5
Continuous
(3 x 551–690 V) [A]
34
41
41
52
52
62
62
83
83
100
Intermittent (60 sec
overload)
(3 x 551–690 V) [A]
51
45.1
61.5
57.2
78
68.2
93
91.3
124.5
110
Continuous KVA
(at 550 V) [KVA]
34.3
41.0
41.0
51.4
51.4
61.9
61.9
82.9
82.9
100.0
Continuous KVA
(at 575 V) [KVA]
33.9
40.8
40.8
51.8
51.8
61.7
61.7
82.7
82.7
99.6
Continuous KVA
(at 690 V) [KVA]
40.6
49.0
49.0
62.1
62.1
74.1
74.1
99.2
99.2
119.5
Max. input current
Continuous
(at 550 V) [A]
36
49
49
59
59
71
71
87
87
99
Continuous
(at 575 V) [A]
54
53.9
72
64.9
87
78.1
105
95.7
129
108.9
Max. cable size, line
power, motor, load
share and brake [mm
2
(AWG)]
35 (1/0)
Max. external electrical
fuses [A]
1
80
100
125
160
160
Estimated power loss
at rated max. load [W]
4)
480
592
720
880
1200
Weight,
enclosure IP21, IP 55
[kg]
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
* High overload = 150% torque during 60 s, Normal overload = 110% torque during 60 s
FC 300 Design Guide
4 AutomationDrive FC 300 Selection
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4-13
4