6.1.2 Mechanical Mounting
All Frame Sizes allow side-by-side installation except when a
IP21/IP4X/ TYPE 1 Enclosure Kit
is used (see the
Options and Accessories
section of the
Design Guide).
If the IP 21 Enclosure kit is used on frame size A1, A2 or A3, there must be a clearance between the drives of a minimum of 2 in [50 mm].
For optimal cooling conditions, allow a free air passage above and below the adjustable frequency drive. See table below.
Air passage for different frame sizes
Frame
size:
A1*
A2
A3
A5
B1
B2
B3
B4
C1
C2
C3
C4
a
(mm):
100
100
100
100
100
200
100
200
200
225
200
225
b
(mm):
100
100
100
100
100
200
100
200
200
225
200
225
Table 6.1: * AutomationDrive FC 301 only
1.
Drill holes in accordance with the measurements given.
2.
You must provide screws suitable for the surface on which you want to mount the adjustable frequency drive. Retighten all four screws.
Table 6.2: Mounting frame sizes A5, B1, B2, B3, B4, C1, C2, C3 and C4 on a non-solid back wall, the drive must be provided with a backplate A due to
insufficient cooling air over the heatsink.
6.1.3 Field Mounting
For field mounting the IP 21/IP 4X top/,TYPE 1 kits or IP 54/55 units are recommended.