1) For type of fuse, see the section Fuses.
2) American Wire Gauge.
3) Measured using 16.4 ft [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerance relates to variety in voltage and cable
conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the adjustable
frequency drive and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. (Though
typical, only 4 W extra for a fully loaded control card, or options for slot A or slot B, each.)
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).