Line Power Supply 3 x 525–690 V AC
AutomationDrive FC 302
P400
P500
P560
High/ Normal Load*
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550 V
[kW]
315
400
400
450
450
500
Typical Shaft output at 575 V
[HP]
400
500
500
600
600
650
Typical Shaft output at 690 V
[kW]
400
500
500
560
560
630
Enclosure
IP21
E1
E1
E1
Enclosure IP54
E1
E1
E1
Enclosure
IP00
E2
E2
E2
Output current
Continuous
(at 550 V) [A]
429
523
523
596
596
630
Intermittent (60 sec overload)
(at 550 V) [A]
644
575
785
656
894
693
Continuous
(at 575/690 V) [A]
410
500
500
570
570
630
Intermittent (60 sec overload)
(at 575/690 V) [A]
615
550
750
627
855
693
Continuous KVA
(at 550 V) [KVA]
409
498
498
568
568
600
Continuous KVA
(at 575 V) [KVA]
408
498
498
568
568
627
Continuous KVA
(at 690 V) [KVA]
490
598
598
681
681
753
Max. input current
Continuous
(at 550 V) [A]
413
504
504
574
574
607
Continuous
(at 575 V) [A]
395
482
482
549
549
607
Continuous
(at 690 V) [A]
395
482
482
549
549
607
Max. cable size, line power, mo-
tor and load share [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external electrical fuses
[A]
1
700
900
900
Estimated power loss
at 600 V [W]
4)
5538
6903
7336
8343
8331
9244
Estimated power loss
at 690 V [W]
4)
5818
7249
7671
8727
8715
9673
Weight,
enclosure IP21, IP 54 [kg]
263
272
313
Weight,
enclosure IP00 [kg]
221
236
277
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemp. trip
185°F [85°C]
Power card ambient trip
154°F [68°C]
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
FC 300 Design Guide
4 AutomationDrive FC 300 Selection
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4-17