Line Power Supply 3 x 200–240 V AC
AutomationDrive
FC 301/
AutomationDrive
FC 302
P15K
P18K5
P22K
P30K
P37K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output
[kW]
15
18.5
18.5
22
22
30
30
37
37
45
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP21
C1
C1
C1
C2
C2
Enclosure IP55, 66
C1
C1
C1
C2
C2
Output current
Continuous
(3 x 200–240 V) [A]
59.4
74.8
74.8
88
88
115
115
143
143
170
Intermittent
(60 sec overload)
(3 x 200–240 V) [A]
89.1
82.3
112
96.8
132
127
173
157
215
187
Continuous
KVA (208 V AC) [KVA]
21.4
26.9
26.9
31.7
31.7
41.4
41.4
51.5
51.5
61.2
Max. input current
Continuous
(3 x 200–240 V) [A]
54
68
68
80
80
104
104
130
130
154
Intermittent
(60 sec overload)
(3 x 200–240 V) [A]
81
74.8
102
88
120
114
156
143
195
169
Max. cable size, IP20
[mm
2
(AWG)]
2)
35 (2)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max. cable size, IP
21/55/66 [mm
2
(AWG)]
2)
90 (3/0)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max cable size with line
power disconnect
35 (2)
70 (3/0)
150 (MCM 300)
Max. electrical fuses [A]
1
125
125
160
200
250
Estimated power loss
at rated max. load [W]
4)
624
737
740
845
874
1140
1143
1353
1400
1636
Weight,
enclosure IP21, IP 55, 66
[kg]
45
45
45
65
65
Efficiency
4)
0.96
0.97
0.97
0.97
0.97
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
4 AutomationDrive FC 300 Selection
FC 300 Design Guide
4-2
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4