![Danfoss FC 300 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/danfoss/fc-300/fc-300_design-manual_507599070.webp)
Line Power Supply 3 x 525–600 VAC
AutomationDrive FC 302
P11K
P15K
P18K5
P22K
P30K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
11
15
15
18.5
18.5
22
22
30
30
37
Enclosure IP 21, 55, 66
B1
B1
B2
B2
C1
Enclosure IP20
B3
B3
B4
B4
B4
Output current
Continuous
(3 x 525–550 V) [A]
19
23
23
28
28
36
36
43
43
54
Intermittent
(3 x 525–550 V) [A]
30
25
37
31
45
40
58
47
65
59
Continuous
(3 x 525–600 V) [A]
18
22
22
27
27
34
34
41
41
52
Intermittent
(3 x 525–600 V) [A]
29
24
35
30
43
37
54
45
62
57
Continuous kVA (550 V AC)
[kVA]
18.1
21.9
21.9
26.7
26.7
34.3
34.3
41.0
41.0
51.4
Continuous kVA (575 V AC)
[kVA]
17.9
21.9
21.9
26.9
26.9
33.9
33.9
40.8
40.8
51.8
Max. cable size IP20
(line power, motor, load
share and brake)
[AWG]
2)
[mm
2
]
16(6)
35(2)
Max. cable size IP21, 55, 66
(line power, motor, load
share and brake)
[AWG]
2)
[mm
2
]
16(6)
35(2)
90 (3/0)
Max cable size with line pow-
er disconnect
16(6)
35(2)
Max. input current
Continuous
at 550 V [A]
17.2
20.9
20.9
25.4
25.4
32.7
32.7
39
39
49
Intermittent
at 550 V [A]
28
23
33
28
41
36
52
43
59
54
Continuous
at 575 V [A]
16
20
20
24
24
31
31
37
37
47
Intermittent
at 575 V [A]
26
22
32
27
39
34
50
41
56
52
Max. electrical fuses
1)
[A]
63
63
63
80
100
Environment
Estimated power loss
at rated max. load [W]
4)
225
285
329
700
700
Weight,
enclosure IP21, 55 [kg]
23
23
27
27
27
Weight,
enclosure IP20 [kg]
12
12
23.5
23.5
23.5
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
4 AutomationDrive FC 300 Selection
FC 300 Design Guide
4-10
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
4