Troubleshooting by Error Code
SiME341909EA
176
Part 6 Service Diagnosis
5.12 Defective Capacity Setting
Applicable
Models
All indoor unit models
Error Code
AJ
Method of Error
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Error Decision
Conditions
The capacity code is not saved to the PCB, and the capacity setting adaptor is not connected.
A capacity that does not exist for that unit is set.
Supposed
Causes
The capacity setting adaptor was not installed.
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the indoor unit control
PCB (A1P).
Replace the indoor unit control
PCB (A1P).
NO
NO
YES
YES
Install a capacity setting
adaptor.
The
indoor unit PCB was replaced
with a spare PCB.
The
capacity setting
adaptor was installed when
replacing the PCB.
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...