Troubleshooting by Error Code
SiME341909EA
210
Part 6 Service Diagnosis
5.34 Outdoor Fan PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
H7
Method of Error
Detection
Detect according to values detected with current sensor.
Error Decision
Conditions
When the current sensor is abnormal.
Supposed
Causes
Disconnection/Short circuit in fan motor leads or disconnection of connector
Defective fan PCB (A4P, A7P)
Troubleshooting
Replace the defective fan motor.
NO
YES
Check for fan motor applicable to the error code
H7
while in monitor mode.
• Sub code
Fan PCB (A7P): H07-21 (Master), H7-23 (Slave 1), H7-25 (Slave 2)
Fan PCB (A4P): H07-22 (Master), H7-24 (Slave 1), H7-26 (Slave 2)
Replace the defective fan PCB.
RXQ6/8AR: A4P
RXQ10-16AR: A4P, A7P
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is
resistance
between Vcc-UVW
and between GND-UVW
of the fan motor lead
in balance?
Turn OFF the power supply
and wait for 10 minutes.
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...