Symptom-based Troubleshooting
SiME341909EA
138
Part 6 Service Diagnosis
2. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and then
replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker is
in its tripped position, do not turn
ON the power supply.
Power failure
After the power failure is reset,
restart the system.
The connector loose or not fully
plugged in
Turn off the power supply to verify
the connection of the connector.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool or heat air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to LOW
Set it to a proper airflow rate.
Improper direction of air diffusion
Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
IN COOLING
Direct sunlight received
Hang curtains or shades on
windows.
IN COOLING
Too many people staying in a room
The model must be selected to
match the air conditioning load.
IN COOLING
Too many heat sources (e.g. OA
equipment) located in a room
4
The system does
not operate.
The system stops and
immediately restarts
operation.
If the operation lamp on the remote
controller turns ON, the system will
be normal. These symptoms
indicate that the system is
controlled so as not to put
unreasonable loads on the system.
Normal operation. The system will
automatically start operation after a
lapse of five minutes.
Pressing the temperature
setting button immediately
resets the system.
The system stops immediately
after turning ON the power
supply.
The system is in preparation mode
of microcomputer operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent
stops.
The remote controller displays
error codes
U4
or
U5,
and the
system stops but restarts after
a lapse of several minutes.
The system stops due to an
interruption in communication
between units caused by electrical
noises coming from equipment
other than air conditioners.
Remove causes of electrical noises.
If these causes are removed, the
system will automatically restart
operation.
6
The system
conducts fan
operation but not
cooling
operation.
This symptom occurs
immediately after turning ON
the power supply.
The system is in preparation mode
of operation.
Wait for a period of approximately
10 minutes.
The remote controller displays
the mark for centralized
control; no cooling operation is
performed. Switch to fan
operation.
In thermal storage operation, the
unit is set to fan operation in cooling
operation, and the remote controller
shows the mark for centralized
control
.
Normal operation.
7
The airflow
direction is not
reproduced
according to the
setting.
The airflow direction is not
corresponding to that
displayed on the remote
controller.
The flap does not swing.
Automatic control
Normal operation.
O
N
Kno
b
Tripped
OFF
Circ
u
it
b
reaker
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...