Field Settings for Outdoor Unit
SiME341909EA
124
Part 5 Field Settings and Test Operation
Mode 2-39:
Emergency operation “Slave 1”
. To disable permanent compressor operation
of “Slave 1” unit of a multi outdoor system:
Default value: 0. Compressor operation enabled.
Field set:
Set 1: Inverter 1 compressor is disabled.
Set 2: Inverter 2 compressor is disabled. Only to make in case of 16-20 HP. Note that
compressor 2 is left side located.
Set 3: All compressors in this master module are disabled permanent.
Mode 2-40:
Emergency operation “Slave 2”
. To disable permanent compressor operation
of “Slave 2” unit of a multi outdoor system:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: Inverter 1 compressor is disabled.
Set 2: Inverter 2 compressor is disabled. Only to make in case of 16-20 HP. Note that
compressor 2 is left side located.
Set 3: All compressors in this master module are disabled permanent.
Combination table setting 2-38, 2-39 and 2-40:
Mode 2-51:
Master/Slave setting Multi
. When 2 or 3 modules are installed as a
multi-outdoor (by common refrigerant piping and wiring by terminals Q1Q2) configuration is
automatically detected. In certain cases, the sequence of the slave units need to be set
manually (in case of AIRNET monitoring).
Default value: 0. Automatic detection.
Field setting: ensure that the modules in a multi are set different status. Even some
modules in a multi are set manually to same status,
U7
error will appear.
1: Forced Master (F1F2/Ind terminals should be connected to indoor units).
2: Forced Slave 1 (only Q1Q2 terminals should be wired to Master module).
3: Forced Slave 2 (only Q1Q2 terminals should be wired to Master module).
Mode 2-81:
Cooling comfort setting
. The comfort level is related to the timing and the
effort (power consumption) which is put in achieving a certain room temperature by changing
temporally the refrigerant temperature to different values in order to achieve requested
conditions more quickly.
Default value: 1 (Mild). Undershoot during cooling operation is allowed compared to the
requested refrigerant temperature, in order to achieve the required room temperature
very fast. The undershoot is not allowed from the startup moment. The startup occurs
under the condition which is defined by the operation mode. In case of cooling operation
the evaporating temperature is allowed to go down to 6°C on temporary base depending
on the situation. When the request from the indoor units becomes more moderate, the
system will eventually go to the steady state condition which is defined by the operation
method above. The startup condition is different from the powerful and quick comfort
setting.
Field setting:
0: Eco. The original refrigerant temperature target, which is defined by the Te setting
(field setting 2-8) in cooling mode, is kept without any correction, unless for protection
control.
disable
Master/
individual
Slave 1
Slave 2
compressor 1
2-38-1
2-39-1
2-40-1
compressor 2
2-38-2
2-39-2
2-40-2
module
2-38-3
2-39-3
2-40-3
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...