Field Settings for Outdoor Unit
SiME341909EA
116
Part 5 Field Settings and Test Operation
2.6.1 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
Do not change contents.
2.
0
0
—
—
—
—
1
Do not change contents.
2.
0
1
—
—
—
—
2
Low noise/
demand address
Used to make address setting for low
noise/demand address.
2.
0
2
Address:
0
~
31
3
0
1
3
Do not change contents.
2.
0
3
—
—
—
—
4
Do not change contents.
2.
0
4
—
—
—
—
5
Indoor fan
forced H
Used to force the fan of indoor unit to H
tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat ON
Used to force all indoor units to operate
forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
7
Do not change contents.
2.
0
7
—
—
—
—
8
Te setting
Used to make setting of targeted
evaporating temperature for cooling
operation.
2.
0
8
Standard: 6°C
High sensible: 7°C
High sensible: 8°C
High sensible: 9°C
High sensible: 10°C
High sensible: 11°C
2
3
4
5
6
7
9
Do not change contents.
2.
0
9
—
—
—
—
10 Do not change contents.
2.
1
0
—
—
—
—
11
Eco setting is available from an external input.
When this configuration is set, it is not possible to turn the
Eco refrigerant control ON/OFF using the remote
controller. Also, depending on the settings, low noise
operation or demand operation may not be performed
using the external control adaptor.
2.
1
1
Unavailable
Low noise level input
Demand input
0
1
2
12
External low
noise/demand
setting
Used to receive external low noise or
demand signal.
2.
1
2
Input LNO/DE
OFF
ON
0
1
13
AIRNET
address
Used to set address of AIRNET
2.
1
3
Address:
0
~
63
6
0
3
15 Do not change contents.
2.
1
5
—
—
—
—
16 Do not change contents.
2.
1
6
—
—
—
—
17 Do not change contents.
2.
1
7
—
—
—
—
18 High EST for
outdoor fan
High external static pressure setting for
outdoor fan
2.
1
8
OFF
ON
0
1
19 Do not change contents.
2.
1
9
—
—
—
—
21
Refrigerant
recovery/
vacuuming
Used to set the system to refrigerant
recovery mode (without compressor
run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic
night-time low
noise operation
Automatic night-time low noise
operation. Time for the operation is
subject to the start and end time
settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
Level 4
0
1
2
3
4
23
Used to set Eco mode invalid.
When this configuration is set, it is not possible to turn the
Eco mode ON/OFF using the external control adaptor.
2.
2
3
Valid
Invalid
0
1
24 Do not change contents.
2.
2
4
—
—
—
—
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...