SiME341909EA
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
101
1.4.26 Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected by duct directly. The
indoor fan carries out residual operation for 1 minute after the thermostat is stopped. (For the
purpose of preventing dust on the air filter from falling off.) When the second code No. is set to
02
: Equipped, heat reclaim ventilation fan conducts the fan residual operation by linking to
indoor unit.
: Factory setting
1.4.27 Drain Pump and Humidifier Interlock Selection
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
: Factory setting
1.4.28 Individual Ventilation Setting
This is set to perform individual operation of heat reclaim ventilation using the remote
controller/central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
: Factory setting
1.4.29 Display of Error Codes on the Remote Controller
BRC1E Series
Error code (four digits) is displayed for limited products. Select two-digit display if four-digit
display is not preferred.
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
2
01
Not equipped
02
Equipped
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
5
01
— (Normal)
02
Individual
Mode
No.
First
Code No.
Second
Code No.
Contents
1b
4
01
―
02
Two-digit display
03
―
04
Four-digit display
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...