Field Settings for Indoor Unit
SiME341909EA
88
Part 5 Field Settings and Test Operation
1.2 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(
∗
2
)
First
Code
No.
Description
Second Code No.
Page
Reference
01
02
03
04
10 (20)
0
Filter cleaning
sign interval
Long life filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Ultra long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
1
Filter type
Long life filter
Ultra long life filter
—
—
2
Remote controller thermistor
Remote
controller
ther
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
3
Filter cleaning sign
Displayed
Not displayed
—
—
6
Remote controller thermistor
control during group control
Not permitted
Permitted
—
—
7
Time for absence area detection
30 minutes
60 minutes
—
—
10
Dry operation time during
VRTsmart control
30 minutes
60 minutes
90 minutes
Continuous
(not
returning to
cooling)
11
Low airflow setting when
thermostat OFF during
VRTsmart control
Disabled
Enabled
—
—
11 (21)
6
Setting the rate of human
detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
7
Automatic airflow adjustment
OFF
Completion of
airflow adjustment
Start of
airflow
adjustment
—
8
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
12 (22)
0
Optional accessories output
selection
Indoor unit
turned ON by
thermostat
—
Operation
output
Error output
1
External ON/OFF input
Forced OFF
ON/OFF control
External
protection
device input
—
2
Thermostat differential
changeover
1°C
0.5°C
—
—
5
Auto restart after power failure
OFF
ON
—
—
6
Airflow setting when cooling
thermostat is OFF
LL tap
Set fan speed
—
—
11
Compensating the floor
temperature (cooling)
4°C
2°C
0°C
–2°C
13 (23)
0
Ceiling height setting, Setting of
normal airflow
Refer to the page on the right for details.
1
Airflow direction setting
4-way airflow
3-way airflow
2-way airflow
—
2
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
3
(
∗
5)
Airflow function setting
Equipped
Not equipped
—
—
—
4
Airflow direction adjustment
range
Refer to the page on the right for details.
5
Setting of static
pressure selection
Standard
High static
pressure
—
—
6
External static pressure settings
Refer to the page on the right for details.
7
Setting of swing patterns when
cooling thermostat is OFF
Refer to the page on the right for details.
13
Setting of circulation airflow
Disabled
Enabled
—
—
14
Circulation airflow patterns
Pattern 1
Pattern 2
Pattern 3
Pattern 4
15
Switching panel type
Standard panel
Designer panel
—
—
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...