SiME341909EA
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
97
Note(s)
Note(s)
1.4.15 Compensating the Floor Temperature (Cooling)
(For units with the infrared presence/floor sensor)
Offset the detected value of the infrared presence/floor sensor with a certain temperature. This
setting should be used to have the actual floor temperature detected when, for example, the unit
is installed close to a wall.
: Factory setting
Specific usages of this setting
There is no problem with the standard setting in the usual condition. Change the setting in the
cases indicated in the following table.
This setting is available only in cooling operation.
1.4.16 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to
01
at
the factory.
FXFSQ25-80AR
: Factory setting
FXFSQ100-140AR
: Factory setting
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or
(2), initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
11
01
4°C
02
2°C
03
0°C
04
–2°C
Environment
Operation
Mode
Problem
Contents
-The unit is installed close to a wall or a
window.
-High thermal capacity of the floor (such as
concrete, etc).
-There are many heat sources including PC.
-There is a non-negligible heat source such as
floor heating.
Cooling
Insufficient cooling
–2°C
Excessive cooling
2°C or 4°C
Mode
No.
First
Code No.
Second
Code No.
Contents
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower
than
2.7 m
Lower
than
3.1 m
Lower than
3.0 m
Lower than
3.5 m
02
High
Ceiling(1)
Lower than
3.0 m
Lower than
3.4 m
Lower than
3.3 m
Lower than
3.8 m
03
High
Ceiling(2)
Lower than
3.5 m
Lower than
4.0 m
Lower than
3.5 m
—
Mode
No.
First
Code No.
Second
Code No.
Contents
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower
than
3.2 m
Lower
than
3.4 m
Lower than
3.6 m
Lower than
4.2 m
02
High
Ceiling(1)
Lower than
3.6 m
Lower than
3.9 m
Lower than
4.0 m
Lower than
4.2 m
03
High
Ceiling(2)
Lower than
4.2 m
Lower than
4.5 m
Lower than
4.2 m
—
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...