SiME341909EA
Symptom-based Troubleshooting
Part 6 Service Diagnosis
141
2.2 For All Outdoor Units
Problem
Measure
Decrease of main circuit power supply insulation
resistance (Less than 1 M
Ω
)
Define the measure using the flowchart below.
1 M
Ω
or more?
YES
YES
NO
NO
Decrease of main circuit power supply
insulation resistance
Cut the power supply.
Cut the power supply.
Defective local power supply
Normal
Remove the compressor wiring from the
power supply terminal. Isolate the wiring
and be careful not to touch the live parts.
Turn the power supply on and leave it on
for 6 hours (keep the compressor wiring
disconnected).
Connect the compressor wiring to the
terminal, or to the noise filter PCB and
measure the insulation resistance.
1 M
Ω
or more?
Measure the insulation resistance of the
main circuit power supply.
Check the local power supply.
Compressor abnormality
Replace the compressor.
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...