Troubleshooting by Error Code
SiME341909EA
186
Part 6 Service Diagnosis
5.20 Infrared Presence/Floor Sensor Error
Applicable
Models
FXFSQ-AR
Error Code
CE
Method of Error
Detection
The contents of a failure vary with the detailed error code. Check the code and proceed with the
flowchart.
Error Decision
Conditions
Error is detected based on sensor output signals
Supposed
Causes
Defective or disconnected infrared presence sensor connector:
CE-01
Defective infrared floor sensor (Temperature compensation circuit disconnection):
CE-02
Defective infrared floor sensor (Temperature compensation short circuit):
CE-03
Defective infrared floor sensor element:
CE-04
Troubleshooting
See diagnosis procedure 2.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error code
CE-02
See diagnosis procedure 3.
Error code
CE-03
See diagnosis procedure 4.
Error code
CE-04
Error type varies according
to error code. Check the
error code and take the
following steps.
See diagnosis procedure 1.
Error code
CE-01
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...