SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
235
Reference
Reference
Reference
5.49 Refrigerant Shortage Warning
Applicable
Models
All outdoor unit models
Error Code
U0
Sub code: 05
Method of Error
Detection
Detects refrigerant shortage according to the ending conditions of cooling oil return control.
Error Decision
Conditions
Cooling oil return control does not finish according to the ending conditions, and the time is
up for 3 consecutive times.
∗
No abnormality is determined, and the operation continues.
Supposed
Causes
Refrigerant shortage and refrigerant clogging (wrong piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB
Troubleshooting
CHECK 2
Refer to page 262.
CHECK 3
Refer to page 263.
CHECK 7
Refer to page 267.
Replace the thermistor.
NO
Replace the outdoor unit
main PCB (A1P).
YES
YES
Are the
characteristics of the
suction air thermistor
normal?
NO
Are the
characteristics of the
low pressure sensor
normal?
Replace the low pressure
sensor.
Correct the abnormally low
pressure.
Correct the insufficient low
refrigerant condition.
Correct the superheat
operation.
NO
YES
Is refrigerant shortage detected
as a cause of abnormally
low pressure?
NO
YES
YES
YES
Is refrigerant
insufficient?
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
CHECK 2
Is another cause detected as a
cause of abnormally low
pressure?
CHECK 2
Is refrigerant shortage detected
as a cause of superheat
operation?
CHECK 3
CHECK 7
Is another cause detected
as a cause of superheat
operation?
CHECK 3
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...