Troubleshooting by Error Code
SiME341909EA
208
Part 6 Service Diagnosis
Reference
5.32 Refrigerant Overcharged
Applicable
Models
All outdoor unit models
Error Code
F6
Method of Error
Detection
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger liquid pipe
temperature, and subcooling heat exchanger liquid pipe temperature during test operation.
Error Decision
Conditions
When the amount of refrigerant, which is calculated using outdoor air temperature, heat
exchanger liquid pipe temperature, and subcooling heat exchanger liquid pipe temperature
during test operation, exceeds the regular charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount,
F6
may be displayed on the
remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of outdoor air thermistor
Disconnection of heat exchanger liquid pipe thermistor
Disconnection of subcooling heat exchanger liquid pipe thermistor
Troubleshooting
CHECK 11
Refer to page 269.
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
liquid pipe thermistor, and
subcooling heating exchanger
liquid pipe thermistor to the piping.
Disconnect the outdoor air
thermistor, the heat exchanger
liquid pipe thermistor, and
subcooling heating exchanger
liquid pipe thermistor from the
outdoor unit main PCB, and
then make measurement of
resistance using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the temperature
sensors properly
mounted?
CHECK 11
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...