SiME341909EA
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
117
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
25
External
night-time low
noise operation
level
Low noise level when the external low
noise signal is input at option
DTA104A61.
2.
2
5
Level 1
Level 2
Level 3
Level 4
1
2
3
4
26
Automatic
night-time low
noise operation
start
Time to start automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2.
2
6
About 8:00 PM
About 10:00 PM
About 12:00 AM
1
2
3
27
Automatic
night-time low
noise operation
stop
Time to stop automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2.
2
7
About 6:00 AM
About 7:00 AM
About 8:00 AM
1
2
3
28
Power transistor
check
Used to troubleshoot DC compressor.
Inverter waveforms are output without
wire connections to the compressor. It is
useful to determine whether the relevant
trouble has resulted from the
compressor or inverter PCB.
2.
2
8
OFF
ON (10 Hz)
0
1
29
Capacity priority Cancel the low noise level control if
capacity is required while low noise
operation or night-time low noise
operation is in progress.
2.
2
9
OFF
ON
0
1
30
Demand 1
setting
Used to make a change to the targeted
power consumption level when the
demand 1 control signal is inputted.
2.
3
0
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
1
2
3
4
5
6
7
8
31
Demand 2
setting
Used to use a targeted power current
level when the demand 2 control signal
is inputted.
2.
3
1
Level 1 (40%)
Level 2 (50%)
Level 3 (55%)
1
2
3
32
Constant
demand setting
Used to set constant demand 1 or 2
control without inputting any external
signal.
2.
3
2
OFF
Demand 1 (Mode 2-30)
Demand 2 (Mode 2-31)
0
1
2
33 Do not change contents.
2.
3
3
—
—
—
—
34 Do not change contents.
2.
3
4
—
—
—
—
35 Do not change contents.
2.
3
5
—
—
—
—
36 Do not change contents.
2.
3
6
—
—
—
—
37 Do not change contents.
2.
3
7
—
—
—
—
38
Emergency
operation
(master)
To prohibit a compressor or complete in
“Master”. Since module is permanent
disabled, immediately replace the
defective component(s).
2.
3
8
OFF
Master M1C OFF
Master M2C OFF
Master unit OFF
0
1
2
3
39
Emergency
operation
(slave 1)
To prohibit a compressor or complete
“Slave 1”. Since module is permanent
disabled, immediately replace the
defective component(s).
2.
3
9
OFF
Slave 1 M1C OFF
Slave 1 M2C OFF
Slave 1 unit OFF
0
1
2
3
40
Emergency
operation
(slave 2)
To prohibit a compressor or complete
“Slave 2”. Since module is permanent
disabled, immediately replace the
defective component(s).
2.
4
0
OFF
Slave 2 M1C OFF
Slave 2 M2C OFF
Slave 2 unit OFF
0
1
2
3
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...