Part 6 Service Diagnosis
5.18 Capacity Setting Abnormality
Applicable
Models
FXFSQ-AR
Error Code
C6-01
Method of Error
Detection
This error is detected by checking communication between the PCB (A1P) and the fan
microcomputer.
Error Decision
Conditions
Based on the communication data, decide whether the combination of capacity setting and the
type of fan driver is correct.
Supposed
Causes
Defective connection of the capacity setting adaptor
Wrong field setting
Troubleshooting
Is the indoor
unit PCB (A1P) replaced by
the spare PCB?
After transmission between
the indoor and the outdoor
PCBs is established, perform
operation again and then
perform diagnosis again.
After transmission between
the indoor and the outdoor
PCBs is established, perform
operation again and then
perform diagnosis again.
Is a proper
capacity setting adaptor
installed when replaced by the
space PCB?
Install a proper capacity
setting adaptor.
NO
NO
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV X RXQ6-48ANR Series
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Страница 287: ...SiME341909EA Part 7 Appendix 281 1 Wiring Diagrams 282 1 1 Outdoor Unit 282 1 2 Indoor Unit 285 Part 7 Appendix...
Страница 288: ...Wiring Diagrams SiME341909EA 282 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8ARYFK 3D124186A...
Страница 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Страница 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Страница 292: ...Wiring Diagrams SiME341909EA 286 Part 7 Appendix BYCQ125EASF Auto Grille Panel for FXFSQ AR 3D108035...
Страница 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 296: ...Wiring Diagrams SiME341909EA 290 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32 40 50 63ARVM 3D118250D...