Instruction
SiAU18-715
290
Operation Manual
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING
3. OPERATION RANGE
OUTDOOR
UNIT
INDOOR
OUTDOOR
TEMPERA-
TURE
TEMPERA-
TURE
HUMID
ITY
R35 · 45 · 60
DB 18 to 33 80% or
below
DB – 15 to 46
WB 12 to 24
RY35 · 45 · 60
DB 18 to 33 80% or
below
DB – 5 to 46
WB 12 to 24
R71 · 100 · 125
RP71 · 100 · 125
REP71 · 100 · 125
DB 21 to 35
80% or
below
DB – 15 to 46
WB 14 to 25
RY71 · 100 · 125
RYP71 · 100 · 125
RYEP71 · 100 · 125
DB 18 to 35
80% or
below
DB – 5 to 46
WB 12 to 25
RZP71 · 100 · 125
DB 21 to 35 80% or
below
DB – 5 to 50
WB 14 to 25
RQ71 · 100 · 125
DB 18 to 37 80% or
below
DB – 5 to 46
WB 12 to 28
RR71 · 100 · 125
DB 18 to 37 80% or
below
DB – 15 to 46
WB 12 to 28
RZQ71 · 100 ·
125 ·140
DB 18 to 37 80% or
below
DB – 15 to 50
WB 12 to 28
RS50 · 60
RKS35 · 50 · 60
RXS35 · 50 · 60
DB 21 to 32
80% or
below
DB – 10 to 46
WB 14 to 23
3MKS50
4MKS58 · 75 · 90
3MXS52 · 2MXS52
4MXS68 · 80
DB 21 to 32
80% or
below
DB – 10 to 46
WB 14 to 23
RMKS112 · 140 · 160
RMXS112 · 140 · 160
DB 21 to 32
80% or
below
DB – 5 to 46
WB 14 to 23
HEATING
DB: Dry bulb temperature (˚C)
WB: Wet bulb temperature (˚C)
The setting temperature range of the remote con-
troller is 16˚C to 32˚C.
Regarding places for installation
• Is the air conditioner installed at a well-venti-
lated place where there are no obstacles
around?
• Do not use the air conditioner in the following
places.
a. Filled with much mineral oil such as cutting oil
b. Where there is much salt such as a beach area
c. Where sulfured gas exists such as a hot-spring
resort
d. Where there are considerable voltage fluctua-
tions such as a factory or plant
e. Vehicles and vessels
f. Where there is much spray of oil and vapor
such as a cookery, etc.
g. Where there are machines generating electro-
magnetic waves
h. Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer.
OUTDOOR
UNIT
INDOOR
TEMPERA-
TURE
OUTDOOR
TEMPERATURE
RY35 · 45 · 60
DB 15 to 27
DB
– 9 to 21
WB – 10 to 15.5
RY71 · 100 · 125
RYP71 · 100 · 125
RYEP71 · 100 · 125
DB 15 to 27
DB
– 9 to 21
WB – 10 to 15.5
RZP71 · 100 · 125 DB 15 to 27
DB
– 14 to 21
WB – 15 to 15.5
RQ71 · 100 · 125 DB 10 to 27
DB
– 9 to 21
WB
– 10 to 15
RZQ71 · 100 ·
125 · 140
DB 10 to 27
DB – 19.5 to 21
WB – 20 to 15.5
RXS35 · 50 · 60
DB 10 to 30
DB
– 14 to 24
WB
– 15 to 18
3MXS52 · 2MXS52
4MXS68 · 80
DB 10 to 30
DB
– 14 to 21
WB – 15 to 15.5
RMXS112 · 140 · 160 DB 10 to 30
DB
– 14 to 21
WB – 15 to 15.5
4. INSTALLATION SITE
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...