SiAU18-715
Specifications
Specifications
23
1.2
Heat Pump
1.2.1 Outdoor Units
50Hz 220-230-240V
Note:
1.
★
Refrigerant charge is required. (Chargeless piping length 0m)
Formula for calculation charge : R (kg)
R = Total length (m) of liquid pipe size at
φ
9.5×0.054 + Total length (m) of liquid piping size at
φ
6.4×0.022
2. The data are based on the conditions shown in the table below.
Model
RMXS112EV1A
RMXS140EV1A
RMXS160EV1A
4HP
5HP
6HP
Cooling Capacity
kW
(kcal/h)
11.2 (9,630)
14.0 (12,040)
15.5 (13,330)
Heating Capacity
kW
(kcal/h)
12.5 (10,750)
16.0 (13,760)
17.5 (15,050)
Total Indoor Unit Capacity
kW
5.5~14.5
7.0~18.2
8.0~20.8
Power Consumption
W
—
Running Current
A
—
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Scroll Type
Model
JT100G-VDL
Motor Output
(2.2kW/60rps)
kW
2.5
3.0
3.5
Refrigerant
Oil
Model
DAPHNE FVC68D
Charge
L
1.5
Refrigerant
Type
R-410A
Charge
kg
4.0
Air Flow Rate
(H)
Cooling
m³/min
(cfm)
106 (3,742)
Heating
m³/min
(cfm)
106 (3,742)
Fan
Type
Propeller
Motor Output
W
70+70
Running Current
A
0.4+0.4
Power Consumption
W
88+88
Starting Current
A
20.0-19.2-18.4
24.8-23.7-22.7
26.4-25.2-24.2
Dimensions (H×W×D)
mm
1,345×900×320
Package Dimensions (H×W×D)
mm
1,475×925×390
Weight
kg
125
Gross Weight
kg
136
Operation
Sound
Cooling
dBA
52
53
54
Heating
dBA
54
55
56
Piping
Connection
Liquid
mm
φ
9.5 (Flare Connection)
Gas
mm
φ
19.1 (Brazing Connection)
Drain
mm
φ
18
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 For Power Supply (Including Earth Wiring), 2 For Interunit Wiring (Outdoor Unit-BP)
Total piping
length
O.U. - BP
m
55
BP - I.U.
m
60
80
90
System Total
m
115
135
145
Max. piping
length
BP - I.U.
m
15
1st Branch - I.U.
m
40
Max. level
difference
O.U. - BP
m
30
O.U. - I.U.
m
30
BP - BP, I.U. - I.U.
m
15
Necessity of Additional Charge
★
kg/m
Necessary
Cooling
Heating
Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
Main Piping : 5m
Branch Piping : 3m
Level difference : 0m
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BP Unit
Outdoor Unit
Main Piping
Branch Piping
Indoor Unit
(Q0143)
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...