SiAU18-715
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
337
Troubleshooting
Check No.01
Refer to P.348
NO
YES
Is the
harness from the fan
motor correctly connected to
X20A connector on
A1P?
YES
Is there
any foreign matter
around the fan?
NO
NO
Does
the resistance
between U,V,W
phases of fan motor
balance each other? Is there
short circuit between
U,V,W phases
respectively?
YES
Turn off the power supply.
Check No. 01
Check for the fan motor
connector.
Remove the foreign matter.
Connect correctly.
Replace the fan motor.
Replace the indoor unit PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(Q0535)
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...