Indoor Unit (SkyAir Models)
SiAU18-715
118
Function
1-2 Operations when an occurrence of water level abnormality
1-2-a) Behavior between occurrence and recovery of water level abnormality
Occurrence of drain water level abnormality
5
sec
A
10
sec sec
1-2-b) Behavior when the unit restarts by remote controller after the water level abnormality is recovered
Intermittent operation (*1)
5min
5min
Compressor
ON
OFF
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
Error processing
Abnormal
Normal
After compressor stops due to water level abnormality, drain pump is operated intermittently, i.e. 5 min
ON, 5 sec OFF and 5 min ON. (*1) The intermittent operation is executed regardless of recovery of water
level abnormality during the intermittent operation. (*2) When the water level abnormality can not be
recovered, the latter 5 min ON operation is continued until recovery of the abnormality. (*3)
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Water level abnormality shall be cancelled simultaneausly when the unit is turned off with remote controller
after recovery of the water level abnormality. When the unit is turned on with remote controller thereafter,
compressor starts operation 2 minutes later from the remote controller ON. (Below diagram shows an
example of the case that the water level abnormality is recovered during the former 5 min intermittent
operation.)
Occurrence of drain water level abnormality
5
sec
A
10
sec sec
Compressor starts operation after 2 minutes from
remote controller ON.
(When 3-min standby of compressor is complete.)
Alarm indication will be turned off with the remote controller
OFF operation after recovery of drain water level abnormality.
Recovery of drain water level abnormality
ON
2 min
Compressor
ON
OFF
Error processing
Abnormal
Normal
Remote controler
5min
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
OFF
Note : (1 On the whole of cooling and dry operation)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...