SiAU18-715
Field Setting
Test Operation
139
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
1
Cool / Heat
Unified address
8
7
7
7
7
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
3
Test operation
8
7
7
7
7
8
8
Test operation : OFF
8777778
Test operation : ON
8777787
∗
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9
Tc setting
8
7
7
8
7
7
8
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10
Defrost changeover
setting
8
7
7
8
7
8
7
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8888888
16
Setting of hot water
heater
8
7
8
7
7
7
7
OFF
8777778
∗
ON
8777787
20
Additional refrigerant
charging operation
setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant recovery /
vacuuming mode
setting
8
7
8
7
8
7
8
Refrigerant recovery /
vacuuming: OFF
8777778
∗
Refrigerant recovery /
vacuuming: ON
8777787
22
Night-time low noise
setting
8
7
8
7
8
8
7
OFF
8777777
∗
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
Level 3 (outdoor fan with 6 step or lower)
8777788
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...