SiAU18-715
Troubleshooting for Outdoor Unit
Troubleshooting
391
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has the
indoor or
outdoor unit PC
board been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been
modified?
All indoor unit
remote controllers of the
same refrigerant system
display "U4."
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
Outdoor
unit PC board
microcomputer monitor
(HAP) blinks.
Reset the power supply.
Is indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
The
voltage
between terminals
L1 and N of the outdoor
unit PC board is
220~240 V.
The fuse on
the outdoor unit's PC
board is burnt.
The secondary
voltage of the transformer
is about 22~24 V.
Operation
ready lamp (H2P) is
blinking.
Lamp does
not go off for 12 minutes
or more.
NO
Fix the indoor/outdoor unit
transmission wiring.
NO
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
YES
NO
Replace the indoor unit
PC board.
Supply 220~240 V.
Fix the indoor/outdoor unit
transmission wiring.
Push and hold the RESET
button on the master
outdoor unit PC Board for
5 seconds.
∗
The unit will not operate
for up to 12 minutes.
YES
YES
NO
Replace outdoor unit PC
board (A1P).
YES
NO
NO
YES
YES
Replace the outdoor unit
PC board (A1P).
YES
(Q0578)
YES
NO
NO
Replace the fuse.
NO
YES
YES
Replace the transformer.
NO
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...