Indoor Unit (SkyAir Models)
SiAU18-715
120
Function
2-2-a)-2 When a water level abnormality occurs during drain pump OFF
Occurrence of drain water level abnormality
5
sec
A
sec 80 sec
5min
5min
OFF
Drain pan
Water level abnormality
Normal
Error processing
Abnormal
Normal
Intermittent operation (*1)
Drain pump
ON
OFF
Compressor
ON
The abnormality is determined when 80 seconds elapse from compressor stop. Other than above,
behavior is same as 2-2-a).
Note : ((2-2-a)-2 When a water level abnormality occurs during drain pump OFF)
Recovery operation for drain water level abnormality does not activate when the water level can be
returned normal within A + 80 seconds.
2-2-b) Behavior when the unit restarts by remote controller after the water level abnormality is recovered
Occurrence of drain water level abnormality
5
3
sec
min
A
10
sec sec
Compressor starts operation after 2 minutes from
remote controller ON.
(When 3-min standby of compressor is complete.)
Alarm indication will be turned off with the remote controller OFF
operation after recovery of drain water level abnormality.
Recovery of drain water level abnormality
5min
5min
Intermittent operation (*1)
Drain pan
Water level abnormality
Normal
Remote controler
ON
OFF
Drain pump
ON
OFF
Compressor
ON
OFF
Error processing
Abnormal
Normal
2 min
20 min
20min
Basic operation
Abnormal water level shall be cancelled simultaneausly when the unit is turned off with remote controller
after recovery of abnormal water level. When the unit is turned on with remote controller thereafter,
compressor starts operation 2 minutes later from the remote controller ON. (Below diagram shows an
example of the case that the water level abnormality is recovered during the former 5 min intermittent
operation after the abnormality occurred during drain pump ON.)
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...