Indoor Unit (RA Models)
SiAU18-715
102
Function
7.2
Fan Speed Control
for Indoor Units
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and
Hall IC
control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 324.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
In automatic operation, the step “SL” is not available.
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Note:
1. Fan stops during defrost operation.
2. In time of thermostat OFF, the fan rotates at the following speed.
Cooling : The fan keeps rotating at the set tap.
Heating : The fan stops.
Automatic Air
Flow Control for
Heating
On heating mode, the indoor fan speed will be regulated according to the indoor heat exchanger
temperature and the difference between the room temperature and the required set point.
Automatic Air
Flow Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
Wall mounted type 50-60
class
Wall mounted type 20-35
class, 71 class
Duct connected type
Floor/ceiling suspended
type
Floor standing type
Step
Cooling
Heating
Cooling
Heating
Cooling
Heating
LLL
LL
L
ML
M
MH
H
HH (Powerful)
H+90
H+90
H+50
H+50
H+40
H+40
(R6037)
(R6834)
(R6037)
(R6834)
(R6833)
(R6834)
+1.5˚C
+0.5˚C
+2˚C
+1˚C
M
ML
L
fan speed
Difference between room
and set temperature
Thermostat
setting
temperature
(R4594)
DC motor: Rotation speed control
AC motor: Phase control
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...