Protection Control
SiAU18-715
90
Function
4.2
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
[In heating operation]
Pe
<
0.25MPa
36Hz Unload
Pe
>
0.39MPa
Pe
<
0.07MPa
Low pressure not limited
Low pressure
standby
Low pressure
limited
Pe: LP pressure sensor detection
value
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.
Pe<0.15MPa Pe>0.30MPa
Hot gas SVP = OFF
Hot gas SVP = ON
&
• Ts-Teg<8deg
• Pe>0.06MPa
• Pe>0.09MPa
or
After 10 sec.
Pe<0.17MPa
Pe<0.17MPa
Pe>0.20MPa
Pe
<
0.07MPa
Current step limited
After 15 sec.
Low pressure not limited
Low pressure limited
INV upper limit frequency :
1-step up from current
compressor frequency
Pe: LP pressure sensor detection
value
INV upper limit frequency :
3-step down from current
compressor frequency
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.
Low pressure
standby
Pe<0.12MPa Pe>0.17MPa
Hot gas SVP = OFF
Hot gas SVP = ON
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...