SiAU18-715
Field Setting
Test Operation
151
3.2.6
Check Operation
To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping
length, refrigerant overcharging, and learning for the minimum opening degree of electronic
expansion valve.
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
8
:
ON
3
:
OFF
9
:
BLINK)
3383333
3933338
Pressure equalizing
Step 1
20 sec to 2 minutes
10 minutes
3 minutes
15 minutes
3933383
Cooling start control
Step 2
3933388
3933888
Stability waiting operation
Step 3
Refrigerant over charge judgment
Step 7
•
Stop valve close check
•
Wrong wiring check
•
Piping length check
3933833
3933838
3933883
Judgment function
Step4~6
CHECK OPERATION FUNCTION
5 seconds
3938338
3938383
Pump down residual operation
Step 8
2 minutes
Standby for restarting
Completion
Step 9
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...