Troubleshooting for Outdoor Unit
SiAU18-715
388
Troubleshooting
Troubleshooting
Check No.03
Refer to P.404
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the power
supply voltage
200~240V ±10%?
Is the P-N
resistance not less
than several hundred
of ohms?
Check No.03
Is the resistance above
standard value?
Is the
measured voltage 220
VDC or more?
Correct power supply
Field factors
Replace the inverter PC
board (A1P).
(Q0576)
YES
YES
YES
NO
NO
Replace the fan motor
NO
Monitor the voltage
(Instantaneous voltage
drop)
YES
NO
When the compressor is
running, measure the voltage
b and - of
electrolytic capacitor (C+, C-).
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...