Basic Control
SiAU18-715
80
Function
Heating Operation
TcS = TcS initial value + KTc2
KTc2 : Correction value by
∆
D signal in heating.
KTc2 = 0
(without correction)
∆
D control
Keep the current KTc2
KTc2 = KTc2 + 0.5
KTc2 = KTc2 - 0.5
Up control by
∆
D signal
continues 120 sec.
Down control by
∆
D signal
continues 120 sec.
During compressor frequency PI
control (KTc2 = 0)
Not during compressor frequency PI
control
(Q0397)